Zone expander RS-202SX8
Reservation is needed
Designed to increase the number of loop circuits of security and fire alarm. Is used in conjunction with object device RS-202TP8. |
Specifications:
- Informational capacity:
- 8 reprogrammable loop circuits security and fire alarm with detection of short-circuit, circuit break and option to switch off power supply
- Type of loop circuits: with 5.6 kOhm terminal resistor
- Loop circuit voltage: 12 V
- Arming/disarming: from control device
- Device connection line: RS-485
- Time for detecting comunication loss with device: 2 sec
- Tamper for detection of case breaking up
- Supply voltage: from 10 to 15 V
- Dimensions: 160 х 110 х 32 mm